2.7.4 LV Direct Parallel Connection WITH Certified Inverter BMS Communication (Closed-Loop)
Note that for installations WITH certified Inverter BMS Communications the maximum number of battery
modules per installation is limited to seven clusters of fifteen Battery Modules per cluster. The DD21001 Low
Voltage Hub must be used when the installation has more than one cluster.
Individual Module Setting
Standard Discharging Current
Warranty Terms Charge Current
50 Adc @ 77°F (25°C) 80% DoD
Warranty Terms Discharge Current
50 Adc @ 77°F (25°C) 80% DoD
DC Voltage (extreme)
BMS Safety Intervention Voltage Limits
-13°F to +149°F (-25°C to +65°C)
+19.4°F to +32°F (-7°C to 0°C)
Charging Temp @ Max 0.25C
+32°F to +113°F (0°C to +15°C)
+59°F to +131°F (+15°C to +55°C)
Discharging Temp @ Max 0.5C
+149°F to +131°F (+65°C to +55°C)
Discharging Temp @ Max 1C
+131°F to +32°F (+55°C to 0°C)
Discharging Temp @ Range 0.1C to 0.5C
+32°F to +19.4°F (0°C to -7°C)
Discharging Temp @ Max 0.1C
+19.4°F to -13°F (-7°C to -25°C)
1% self-discharge per month @ 77°F (25°C)
Performance Warranty Period
10 Years – see Limited Warranty terms