14.3.14 SOurce:FUnction:RSD<wsp><boolean>
The command SOurce:FUnction:RSD<wsp>{ON|1}or abbreviated SO:FU:RSD<wsp>{ON|1} disables
the output of the power supply. The command SOurce:FUnction:RSD<wsp>{OFF|0}or abbreviated
SO:FU:RSD<wsp>{OFF|0} enables the output again.
SOurce:FUnction:RSD?
The query SOurce:FUnction:RSD? or abbreviated SO:FU:RSD? returns 1 when the power supply is
disabled. Otherwise a 0 is returned.
14.3.15 SOurce:FUnction:OUtA<wsp><boolean>
The command SOurce:FUnction:OUtA<wsp>1 or abbreviated SO:FU:OUA<wsp>1 sets the open
collector output A of the PSC-488 to 1.
The command SO:FU:OUtA<wsp>0 sets the open collector output A of the PSC-488 to 0.
SOurce:FUnction:OUtA?
The query SOurce:FUnction:OUtA? or SO:FU:OUA? returns 0 if the digital output A is set to 0.
Otherwise , a 1 is returned.
14.3.16 SOurce:FUnction:OUtB <wsp> <boolean>
The command SOurce:FUnction:OUtB<wsp>1or abbreviated SO:FU:OUB<wsp>1 set the open collector
output B of the PSC-488 to 1.
The command SO:FU:OUA<wsp>0 set the open collector output B of the PSC-488 to 0.
SOurce:FUnction:OUtB?
The query SOurce:FUnction:OUtB? or SO:FU:OUB? returns 0 if the digital output B is set to 0.
Otherwise , a 1 is returned.
14.3.17 SOurce:FUnction:OUTP<wsp>{ON|OFF}
The command SOurce:FUnction:OUTP {on|off} or abbreviated SO:FU:OUTP {on|off} enables (on) or
disables (off) the output of the power supply.
SOurce:FUnction:OUTP?
The query SOurce:FUnction:OUTP? Or SO:FU:OUTP? Returns O when the output is disabled, or 1
when the output is enabled.
14.3.18 SOurce:FUnction:FRontpanel Lock
The command SOurce:FUnction:FRontpanel<wsp>{Lock|Unlock} or SO:FU:FR<wsp> {L|U} locks or
unlocks the front panel pushbuttons. See the power supply manual for details.
SOurce:FUnction:FRontpanel:Lock?
The query SOurce:FUnction:FRontpanel:Lock? Or SO:FU:FR:L? Returns 1 when the front panel is
locked. Otherwise a 0 is returned.
14.3.19 REMote and LOCal
The command REMote switches the power supply to remote-control. The command LOCal switches the
power supply back to manual control.
On some power supplies the selection Remote or Local is done by switches on the power supply itself.
On these power supplies the commands REmote and LOcal have no effect.
page 27 MANUAL May 2008
DELTA ELEKTRONIKA BV PSC SERIES