Chapter 3 Product Specifications
3-11
3_
10EN/15EN
The input device range occupies 20 data registers and output device range 20 data
registers.
10SCM
The input device range occupies 18 data registers.
10DNET
No input device and output device will be occupied.
10PFBS
No input device and output device will be occupied.
10PFBM
The input device range occupies 15 data registers.
10COPM
The input device range occupies 2 data registers.
15SCM
The input device range occupies 18 data registers.
User-defined Addresses
Digital Input/Output Modules
You can assign input devices and output devices to a digital input/output module through HWCONFIG in ISPSoft. The
input devices should be within the range between X0.0 and X511.15, and the output devices should be within the
range between Y0.0 and Y511.15. Take AH16AP11R-5A for example. The default input devices are X0.0~X0.15, and
the default output devices are Y0.0~Y0.15. You can change the input device range from X0.0~X0.15 to X10.0~X10.15,
and change the output device range from Y0.0~Y0.15 to Y20.0~Y20.15.
The default input/output device range: X0.0~X0.15, and Y0.0~Y0.15
The user-defined input/output device range: X10.0~X10.15, and Y20.0~Y20.15