AH Motion Controller Hardware Manual
3-12
_3
Analog Input/Output Modules
You can assign input registers and output registers to an analog input/output module through HWCONFIG in ISPSoft.
The input registers and the output registers should be within the range between D0 and D65535. Take AH06XA-5A
for example. The original input registers are D0~D7, and the original output registers are D8~D11. You can change the
input device range from D0~D7 to D50~D57, and change the output device range from D8~D11 to D100~D103.
The default input/output device range: D0~D7, and D8~D11
The user-defined input/output device range: D50~D57, and D100~D103
Temperature Measurement Modules
You can assign input registers to a temperature measurement module through HWCONFIG in ISPSoft. The input
registers should be within the range between D0 and D65535. Take AH08TC-5A for example. The original input
registers are D0~D15. You can change the input device range from D0~D15 to D60~D75.
The default input device range: D0~D151