ASDA-M Chapter 6 Control Mode of Operation
Revision December, 2014 6-41
P2-45 NCF3
Resonance Suppression (Notch filter)
(3)
Address: 025AH
025BH
Parameter
Attribute
Parameter for individual axis
Related Section:
Section 6.3.7
Operational
Interface
Panel / Software Communication
Default
1000
Control
Mode
ALL
Unit
Hz
Range
50 ~ 2000
Data Size
16bit
Format
DEC
Settings
The third group of mechanism resonance frequency setting value.
If set P2-46 to 0, this function will be disabled. P2-23 and P2-24
are the first group of resonance suppression (Notch filter).
P2-46 DPH3
Resonance Suppression (Notch filter)
Attenuation Rate (3)
Address: 025CH
025DH
Parameter
Attribute
Parameter for individual axis
Related Section:
Section 6.3.7
Operational
Interface
Panel / Software Communication
Default
0
Control
Mode
ALL
Unit
dB
Range
0 ~ 32
Data Size
16bit
Format
DEC
Settings
The third group of resonance suppression (Notch filter)
attenuation rate. Set the value to 0 to disable the function of
Notch filter.