Chapter 8 Parameters ASDA-M
8-80 Revision December, 2014
P2-02 PFG Position Feed Forward Gain
Address: 0204H
0205H
Parameter
Attribute
Parameter for individual axis
Related Section:
Section 6.2.8
Operational
Interface
Panel / Software Communication
Default
50
Control
Mode
PTPR
Unit
%
Range
0 ~ 100
Data Size
16bit
Format
DEC
Settings
If the position command is changed smoothly, increasing the gain
value can reduce the position error.
If the position command is not changed smoothly, decreasing the
gain value can tackle the problem of mechanical vibration.
P2-03 PFF
Smooth Constant of Position Feed
Forward Gain
Address: 0206H
0207H
Parameter
Attribute
Parameter for individual axis
Related Section: -
Operational
Interface
Panel / Software Communication
Default
5
Control
Mode
PTPR
Unit
ms
Range
2 ~ 100
Data Size
16bit
Format
DEC
Settings
If the position command is changed smoothly, decreasing the
value can reduce the position error. If the position command is not
changed smoothly, increasing the value can tackle the problem of
mechanical vibration.

Table of Contents

Other manuals for Delta ASDA-M Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta ASDA-M Series and is the answer not in the manual?

Delta ASDA-M Series Specifications

General IconGeneral
BrandDelta
ModelASDA-M Series
CategoryServo Drives
LanguageEnglish

Related product manuals