Chapter 3 Wiring ASDA-M
3-2 Revision December, 2014
NOTE
Installation Notes:
1) Check if the power and wiring among R, S, T and L1c, L2c are correct.
2) Check if the output terminal U, V, W of the servo motor is correctly wired. The
incorrect wiring may disable the operation of the motor or cause the malfunction.
3) When applying to the external regenerative resistor, the contact between P
and
D should be opened and the external regenerative resistor should connect to
terminal P
and C. When applying to the internal regenerative resistor, the
contact between P
and D should be closed and the contact between P and C
should be opened.
4) When an alarm occurs or the system is in emergency stop status, use ALARM or
WARN to output and disconnect the power of magnetic contactor in order to
disconnect the power of servo drive.