Chapter 12 Description of Parameter SettingsC2000 Plus
12.2-21
If an auto-tuning error (AUE) occurs, refer to Chapter 14 “Fault Codes and Descriptions” for
further treatment.
AUE Error (code) Description
AUE (40) Auto-tuning error
AUE1 (142) Auto-tuning error 1 (No feedback current error)
AUE2 (143) Auto-tuning error 2 (Motor phase loss error)
AUE3 (144) Auto-tuning error 3 (No-load current I
0
measuring error)
AUE4 (148) Auto-tuning error 4 (Leakage inductance Lsigma measuring error)
5. Execute inertia estimation for IM (optional), press RUN key to start the process.
Set Pr.00-10 = 2, torque mode
Set Pr.00-13 = 2, IM TQC sensorless
Set Pr.05-00 = 12, FOC sensorless inertia estimation
Check if the estimated value for Pr.11-01 is reasonable (refer to the explanation of Pr.11-00) when
the inertia estimation process is finished, the base value table of inertia is as below (unit: kg-cm
2
).
HP kW Inertia HP kW Inertia HP kW Inertia
1 0.75 2.3 40 30 202.5 300 220 5139.0
2 1.5 4.3 50 37 355.5 340 250 5981.0
3 2.2 8.3 60 45 410.8 375 280 5981.0
5 3.7 14.8 75 55 494.8 425 315 5981.0
5 4.0 26.0 100 75 1056.5 475 355 5981.0
7 5.5 26.0 125 90 1275.3 530 400 5981.0
10 7.5 35.8 150 110 1900.0 600 450 5981.0
15 11 74.3 175 132 2150.0 675 500 5981.0
20 15 95.3 215 160 2800.0 750 560 5981.0
25 18.5 142.8 250 185 3550.0
30 22 176.5 270 200 5139.0
6. Execute IMFOC Sensorless mode, set up the following parameters:
Set Pr.00-10 = 0, speed mode
Set Pr.00-11 = 5, IMFOC Sensorless
Set Pr.11-00 bit0 = 1, use ASR gain auto-tuning
Press RUN key and start the no load test. Accelerate the motor to the rated speed, and then
decelerate to stop, check if the motor runs smoothly.
If the motor runs smoothly, then the setting for IMFOC Sensorless is completed.
If the motor does not run smoothly or fails to start at low frequency, then refer to the following
steps for adjustment.
7. Select auto-tuning gain (Pr.11-00 bit0 = 1), adjust ASR parameters according to the speed response.
Set Pr.11-00 bit0 = 1, use auto-tuning for ASR
Set Pr.11-03 ASR1 low-speed bandwidth (When the acceleration of low-speed cannot follow the
acceleration command, increase the low-speed bandwidth)
Set Pr.11-04 ASR2 high-speed bandwidth (When the acceleration in high speed causes vibration or
cannot follow the acceleration command, increase high-speed bandwidth)
Set Pr.11-05 Zero-speed bandwidth (If the response of start-up is slow or incapable, increase
zero-speed bandwidth)
The bigger the setting value for ASR bandwidth, the faster the response.
The low-speed bandwidth cannot be set too high, or the observer will diverge.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Plus Series and is the answer not in the manual?

Delta C2000 Plus Series Specifications

General IconGeneral
AltitudeUp to 1000m without derating
CommunicationCANopen
Output Current2.5A
Protection FeaturesOvercurrent, Overvoltage, Overtemperature
Operating Temperature-10°C to 50°C
Storage Temperature-20°C to 60°C
Humidity95% RH (non-condensing)