Chapter 13 Warning CodesC2000 Plus
13-56
ID No. Display on LCD Keypad Warning Name Description
64
CAN/M cycle time-out
(PCCt)
CANopen Master cycle time-out
Action and Reset
Action condition
When the transmitted packet from
CANopen master exceeds the maximum
allowable quantity in a certain time, the PCCt warning displays.
Action time Immediately displays when the fault is detected
Warning setting parameter N/A
Reset method
The warning automatically clears when changing the configuration and re-
executing the program.
Reset condition N/A
Record N/A
Cause Corrective Actions
When the transmitted packet from
CANopen master exceeds the
maximum allowable quantity in a
certain time
Increase the time setting of D1090 synchronization cycle

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta C2000 Plus Series and is the answer not in the manual?

Delta C2000 Plus Series Specifications

General IconGeneral
AltitudeUp to 1000m without derating
CommunicationCANopen
Output Current2.5A
Protection FeaturesOvercurrent, Overvoltage, Overtemperature
Operating Temperature-10°C to 50°C
Storage Temperature-20°C to 60°C
Humidity95% RH (non-condensing)