A.3.3 OD 6000h Communication Object Group
Object 6007hAbort connection option code
Index
6007h
Name
Abort connection option code
Object Type
Variable
Data Type
INTEGER16
Read-Write Permission
RW
PDO MAPPING
SETTING
No
Setting Range
0: No function
2: Switch on Disable
3: Quick Stop
Factory Setting
2
When object 6007h = 0, CANopen ignores a disconnection fault, no warning and do nothing.
When object 6007h =2, CANopen turns to Switch on Disable and displays ECto. CANopen then
follows the setting at object 605Ah to trigger parking. When reconnection is successful, the warning
code disappears.
When object 6007h = 3, CANopen turns to Quick Stop and displays ECto. CANopen then follows
the set=ting at object 605Ch to trigger parking. When reconnection is successful, the warning code
clears.
Object 603FhError code
Index
603Fh
Name
Error code
Object Type
Variable
Data Type
UNSIGNED16
Read-Write Permission
RO
PDO MAPPING
SETTING
Yes
Setting Range
UNSIGNED32
Factory Setting
0
Object 6040hControlword
Index
6040h
Name
Controlword
Object Type
Variable
Data Type
UNSIGNED16
Read-Write Permission
RW
PDO MAPPING
SETTING
Yes
Setting Range
UNSIGNED16
Factory Setting
0