EasyManuals Logo

Delta DVP-PLC User Manual

Delta DVP-PLC
586 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #104 background imageLoading...
Page #104 background image
2 Functions of Devices in DVP-PLC
DVP-PLC Application Manual
2-76
Device No. Cleared Device
M1032
Contact status of M and S for latched
Contact and timing coil of accumulative timer T
Contac and timing coil of high-speed counter C for latched
Present value register of D for latched
Present value register of accumulative timer T
Present value register of high-speed counter C for latched
Function Group
Output Latched During STOP
Number
M1033
Contents:
When M1033 = On and PLC goes from “RUN” to “STOP”, the On/Off status of output will be ratained.
Assume the output contact load of the PLC is a heater, when PLC switches from RUN to STOP, the status of the
heater will be retained. After the PLC program is modified, the PLC will RUN again.
Function Group
All Output Y Inhibited
Number
M1034
Contents:
When M1034 = On, all Y outputs will turn “Off”.
M1034
all outputs inhibited
Function Group
RUN/STOP Switch
Number
M1035, D1035
Contents:
1. When M1035 = On, EH/EH2/SV series MPU will determine the content (K0 ~ K15) in D1035 to enable input
points X0 ~ X17 as the RUN/STOP switch.
2. When M1035 = On, SA/SX/SC series MPU will enable the input point X7 (in SA), X3 (in SX) and X5 (in SC) as
the RUN/STOP switch.
Function Group
Detecting Speed of X0 ~ X5
Number
M1036
Contents:
1. For SC_V1.4 and above, SPD can detect the speed of X0 ~ X5 at the same time. The total bandwidth is 40KHz.
2. Program example:

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta DVP-PLC and is the answer not in the manual?

Delta DVP-PLC Specifications

General IconGeneral
ManufacturerDelta Electronics
ModelDVP-PLC
CategoryController
Humidity5% to 95% RH, non-condensing
Programming LanguageLadder Diagram (LD), Instruction List (IL), Sequential Function Chart (SFC)
CPU TypeVarious, depending on the specific model within the DVP series (e.g., ES2, EX2, SX2, SA2, EH3, etc.)
Operating TemperatureTypically 0°C to 55°C (32°F to 131°F)
Storage TemperatureTypically -25°C to 70°C (-13°F to 158°F)

Related product manuals