9 Application Instructions API 150-199
DVP-PLC Application Manual
9-13
API Mnemonic Operands Function
154
RAND P
Random Number
Controllers
ES/EX/SS SA/SX/SC EH/SV
Bit Devices Word Devices Program Steps Type
OP
X Y M S K H KnX KnY KnM KnS T C D E F
S
1
* * * * * * * * ***
S
2
* * * * * * * * ***
D
* * * * * ***
RAND, RANDP: 7 steps
PULSE 16-bit 32-bit
ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV
Operands:
S
1
: Lower bound of the random number S
2
: Upper bound of the random number D: The random number
produced
Explanations:
1. S
1
S
2
; K0 S
1
, S
2
K32,767
2. See the specifications of each model for their range of use.
3. Entering S
1
> S
2
will result in operation error. The instruction will not be executed at this time, M1067, M1068 =
On and D1067 records the error code 0E1A (hex).
Program Example:
When X10 = On, RAND will produce the random number between the lower bound D0 and upper bound D10 and
store the result in D20.
X10
RAND
D0 D10
D20

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta DVP-PLC and is the answer not in the manual?

Delta DVP-PLC Specifications

General IconGeneral
ManufacturerDelta Electronics
ModelDVP-PLC
CategoryController
Humidity5% to 95% RH, non-condensing
Programming LanguageLadder Diagram (LD), Instruction List (IL), Sequential Function Chart (SFC)
CPU TypeVarious, depending on the specific model within the DVP series (e.g., ES2, EX2, SX2, SA2, EH3, etc.)
Operating TemperatureTypically 0°C to 55°C (32°F to 131°F)
Storage TemperatureTypically -25°C to 70°C (-13°F to 158°F)

Related product manuals