7 Application Instructions API 50-99
DVP-PLC APPLICATION MANUAL
7-47
Lower bound value Upper bound value Present value in C10 Output
D104 = 140 D105 = 170
140 C10 170
M12 = On
D106 = 150 D107 = 390
150 C10 390
M13 = On
5. If the lower bound value > upper bound value, when C10 < upper bound value (60) or > upper bound value (140),
M12 will be On.
Lower bound value Upper bound value Present value in C10 Output
D100 = 40 D101 = 100
40 C10 100
M10 = On
D102 = 120 D103 = 210
120 C10 210
M11 = On
D104 = 140 D105 = 60
60 C10 140
M12 = On
D106 = 150 D107 = 390
150 C10 390
M13 = On
4002000
40
100
120 210
60
140
150 390
M10
M11
M12
M13

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta DVP-PLC and is the answer not in the manual?

Delta DVP-PLC Specifications

General IconGeneral
ManufacturerDelta Electronics
ModelDVP-PLC
CategoryController
Humidity5% to 95% RH, non-condensing
Programming LanguageLadder Diagram (LD), Instruction List (IL), Sequential Function Chart (SFC)
CPU TypeVarious, depending on the specific model within the DVP series (e.g., ES2, EX2, SX2, SA2, EH3, etc.)
Operating TemperatureTypically 0°C to 55°C (32°F to 131°F)
Storage TemperatureTypically -25°C to 70°C (-13°F to 158°F)

Related product manuals