Chapter 6 UPS Display and Settings
80
z
Press the
” and “
buttons simul-
taneously to go back to the “System
Control” menu.
Battery Test OK
Battery Test
FailǺ
Please check
battery aging and make sure
make sure battery
line is normal
6-4. Press the or button to choose Boost chargeand press
button to enter the “Battery Boost charge” setting page.
z
Choose AUTO ON: The UPS controls
itself to execute the boost charge or
not. When the battery voltage is less
than 348V, the UPS will automatically
execute the boost charge.
z
Choose AUTO OFF: The UPS disables
the boost charge function.
Battery
Boost ChargeǺ
AUTO ON
ɥ烉為
ɧ烉炼
z
Press the
” and “
buttons simul-
taneously to go back to the “System
Control” menu.
Manual
Boost ChargeǺ
4Ǻ0 0
ɥ烉為
ɧ烉炼