4. Description of Parameters
4-13
Parameter
code
Function of the parameter Settings
Default
value
VF
FOCPG
FOCPM
a
03-18
Communication error
treatment
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No action and no display
3
a
03-19 Time-out detection 0.0~100.0 seconds 0.0
a
03-20 Start-up display selection
0: F (frequency command)
1: H (actual frequency)
2: Multi-function display (user-defined 00-04)
3: A (Output current)
0
a
03-21
Slave reverse operation for
depressurization
0: Disabled
1: Enabled
0