When the Parameters 03-05 to 03-07 for the multi-function output terminal are set to 45, the motor
fan will start or stop according to this parameter setting.
a
Electronic thermal relay selection 1
Control mode VF FOCPG FOCPM
Factory default: 2
Settings 0: Inverter motor
1: Standard motor
2: Disable
a
Electronic thermal characteristic for motor
Control mode VF FOCPG FOCPM
Factory default: 60.0
Settings 30.0 – 600.0 seconds
To prevent self-cooled motor from over heating at low speed operation, the user can set the
electronic thermal relay to limit the allowed output power of the Hybrid servo drive.
Output frequency at malfunction
Control mode
VF FOCPG FOCPM
Factory default: Read
only
Settings 0.00 – 655.35Hz
Ourput voltage at malfunction
Control mode
VF FOCPG FOCPM
Factory default: Read
only
Settings 0.0 – 6553.5V
DC side voltage at malfunction
Control mode
VF FOCPG FOCPM
Factory default: Read
only
Settings 0.0 – 6553.5V
Ourput current at malfunction
Control mode
VF FOCPG FOCPM
Factory default: Read
only
Settings 0.00~655.35Amp
IGBT temperature at malfunction
Control mode
VF FOCPG FOCPM
Factory default: Read
only
Settings 0.0~6553.5