EasyManuals Logo

DIG 710A Series User Manual

DIG 710A Series
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #33 background imageLoading...
Page #33 background image
31
PROBLEM: The display is blank
CAUSE: No buttons have been pushed in the previous 15 minutes
SOLUTION: Push any button
PROBLEM: Valve fails to close
CAUSE: Valve is installed backwards
SOLUTION: Check flow arrow and verify arrows points away from water source
CAUSE: Debris is blocking solenoid port
SOLUTION: Shut off water supply, unscrew and remove solenoid, then open water
supply and flush out solenoid port, re-install solenoid
PROBLEM: Rain sensor does not prevent watering
CAUSE: Rain sensor is normally open, malfunctioning, or not wired correctly
SOLUTION: Verify that sensor icon appears on display when pin is pushed down &
check all wire splices
PROBLEM: Controller waters more than once per day
CAUSE: More than one start time has been programmed
SOLUTION: Change start time 2,3,4 and 5 to OFF
PROBLEM: Solenoid is not fully closed after using manual operation.
SOLUTION: Lift the controller and turn solenoid clockwise to fully closed position.
PROBLEM: Solenoid or adapter O-rings are damaged or twisted.
SOLUTION: Turn off the water supply. First turn the solenoid counter-clockwise to
remove and inspect the O-ring, and then turn it counter-clockwise and repeat the
inspection. Clean any debris or replace the O-ring as necessary.
For more troubleshooting assistance please visit www.digcorp.com or
call 760-727-0914.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DIG 710A Series and is the answer not in the manual?

DIG 710A Series Specifications

General IconGeneral
BrandDIG
Model710A Series
CategoryController
LanguageEnglish

Related product manuals