12
Scrolltonextscreenstoviewpumpandelectricheathours(optionalifinstalled).
SubMenuD:BMSConfig
UsedonlyforconfigurationsystemtoworkwithSTIICnetwork.
o BMSPort1
o Protocol:Carel
o Adddress 1(Default)
o BaudRate 19200(Default)
SubMenuE:TestMode
o TestMode: Disabled(Default)
o Timeout: Disabled(Default)
SubMenuF:ServiceSettings
SubSubMenuA:WorkingHourSet
o Compressor
o ServiceSetPoint: 0000h(Default) Canbeusedtosetaserviceintervalforsystem.Willdisplay
messageonscreen.
o ResettoZero? NO(Default).
Usedtoresettherunhours
o Runhours: ActualValue. Usedtosettherunhoursifcompressororboardhasbeen
replaced.
Scrolltoviewadditionalitemssuchasthepumpsandelectricheatifinstalled.
SubSubMenuB:ProbeAdjustment
TempSensorCurve:Canselecta
differentsensorforretrofitsthathavethe30ksensor.
o CWReturn: 10k(Default)or30k
o CWSupply: 10k(Default)or30k
o SWInlet: 10k(Default)or30k
Tobeusedforcalibratingtheinstalledtemperaturesensorsorpressuretransducers.
o CWReturn
o InputB001
o Offsett
 0.0(Default)
o Value ActualValue
Scrolltoviewadditionalanalogsensorsforcalibration.
SubSubMenuC:Thermoregulation
Thismenuallowsyoutosetthesuperheatsetpoint.
o Superheat
o CoolSetpoint: 10F(Default)
o HeatSetpoint: 10F(Default)
Nextscreen
o SetpointSH: 10F(Default)
o
LowSHthresh: 2.0F(Default)
o LOPthresh: 30.0F(Default)