13
o MOPthresh: 82.4F(Default)
SubSubMenuD:UserSave
Thisisusedtosaveanyuserspecificsettings.
o Save? No(Default)Yes
o Restore? No(Default)Yes
o EnableAutoSave: Yes(Default)No
SubSubMenuE:StageAddress
Thismenuistobeusedinamultistage
configurationtochangetheadditionalunitaddresses.Thisistobedoneso
thattherearenoaddressconflictswhendaisychainingtheadditionalunitmodbusconnections.Thismustbedone
priortoconnectingalltheunitstogether.
o pLANBoardAddressing
o CurrentAddress: 1(Default)
o ChangeAddress
to:1(Default)
NextScreen
SystemSetup
o NumofStages 1(Default)Max6
SubSubMenu:FStageDisable
Thismenuistobeusedwheninamultistageconfiguration.Thisallowsatechniciantotakeastageofflinesothat
repairscanbemadeandtherest
ofthesystembeoperationalinautomode.Thesystemmustbeinanoffstateto
enablestagecontrol.
o Maintenance
o StageControl: No(Default)Yes.
IfEnabled,
o Stage1: Enabled(Default)Disabled
o Stage2: Enabled(Default)Disabled
o Stage3: Enabled(Default)Disabled
o Stage4:
 Enabled(Default)Disabled
SubMenuG:ManualManagement
Thismenuallowsthetechniciantomanuallyoperatetherelayoutputsaswellasenableordisableanalogsensors.
o SubSubMenuA:AnalogInput
o CWReturn
o ManualControlB001: Off(Default)On
o ManualPosition: ValueDesired
o
Value: ActualValue
Scrolltoadjustadditionalsensors
o SubSubMenuB:DigitalInput
o FlowSwitch
o ManualDI3: Off(Default)ON
o ManualPosition: Actual(EnterDesiredPosition)
o DIInputStatus: ActualValue