%3*45&&.7BQPSMPHJD*OTUBMMBUJPOBOE0QFSBUJPO.BOVBMt1BHF
Calculation of transmitter % RH
% RH =
(mA reading) – 4 mA
16 mA
Example:
12 mA – 4 mA
0.16 mA
Modulating demand signal control
With modulating demand signal control, a modulating humidistat
or a building automation system sends a signal to the Vapor-logic4
controller, which then sends a signal to the humidifier to produce
a directly proportional steam output. For example, if a humidistat
operating between 4 mA and 20 mA sends a 4 mA signal, the
humidifier produces no output; a 12 mA signal causes the
humidifier to run at 50% of capacity; and a 20 mA signal causes
the humidifier to run at 100% capacity.
With a humidistat provided by DRI-STEEM producing this
signal, the humidity set point is set at the humidistat. The
keypad/display then is used for maintaining and troubleshooting
the humidification system, with humidifier control stemming from
the humidistat itself. With a building automation system (BAS)
providing the signal, the humidity set point is established by the
BAS, and the humidifier responds to the BAS commands.
Transmitter control
With transmitter control, the Vapor-logic4 board receives a signal
that corresponds to the actual humidity level measured in the space
being controlled. (With a transmitter provided by DRI-STEEM,
the signal is 4 to 20 mA, which corresponds to 0 to 100% RH). The
Vapor-logic4 controller employs an internal PID loop that uses this
humidity measurement along with a user-defined humidity set
point to calculate a demand level. This demand level is the level at
which the humidifier will run. See “PID tuning” on Page 51.
4UFQo'JFMEXJSJOH
$POUSPMJOQVUTJHOBMT
Installation
x 100%
x 100%
= 50% RH