EasyManuals Logo

DriSteem Vapor-logic 4 User Manual

DriSteem Vapor-logic 4
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #73 background imageLoading...
Page #73 background image
%3*45&&.7BQPSMPHJD*OTUBMMBUJPOBOE0QFSBUJPO.BOVBMt1BHF
5FTUPVUQVUTBOEUFTUSVO
Test outputs
When completing an installation or repair, cycle all outputs,
such as fill valve, drain valve, etc., to verify operation. Go to the
test outputs section of the Diagnostics menu and scroll through
each connected output to verify operation. During testing, the
humidifier mode changes to Standby and the tank status changes
to Test.
Test run
Vapor-logic4 has a test run capability to confirm system
functionality. This capability allows a technician to simulate a
demand for steam production when there isnt one (such as when
performing routine maintenance). To confirm functionality,
go to the test run section of the Diagnostics menu. Set system
demand percent and set test run time duration. During testing, the
humidifier mode changes to Standby and the tank status changes
to Test.
mc_102108_1350
Operation
Not all USB drives perform equally. If a USB flash drive fails
to update the Vapor-logic4 firmware, perform the following
procedure with a different USB flash drive:
1. Prepare a new flash drive as described in Step 3 of
Downloading firmware updates” on Page 65.
2. Repeat Steps 4 through 11 in Table 66-1.
3. Repeat Steps 1 through 7 on Page 68.
mc_120210_1235

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DriSteem Vapor-logic 4 and is the answer not in the manual?

DriSteem Vapor-logic 4 Specifications

General IconGeneral
BrandDriSteem
ModelVapor-logic 4
CategoryController
LanguageEnglish