6
System Outputs (all 12 V
DC)
Other Devices
Read the manufacturer’s literature carefully to determine the maxi-
mum current requirement (during activation or alarm) and use this
value for loading calculations. Do not allow connected devices to
exceed the system capabilities during any possible operational mode.
2.5 Assigning Zones to Zone Expanders
The main panel contains zones 1 to 8. Additional zone expanders
may be added to increase the number of zones on the system. Each
zone expander consists of one group of 8 zones. Each module must
be set to assign the specific zones to the expander. To do this, set
the jumpers located on the expander to the proper settings.
NOTE: Before a zone expander will work properly, you must set the
jumpers so the panel can determine the correct zone assignment.
NOTE: Please see the PC5020 Module Compatibility Chart on the
back cover for compatible versions.
The following are the jumper settings for different zone assign-
ments for PC5108 v2.0 modules. If you need to enroll PC5108
v1.0, PC5108L, PC5700, or PC5720 modules, Refer to the
appropriate module Installation Instruction Sheet for the correct
jumper settings.
he following is a diagram of the PC5108 zone expander module,
showing the location of the jumper switches. Refer to the mod-
ule’s Installation/Instruction Sheet for more information.
NOTE: Only jumpers J1, J2, and J3 determine the zone assign-
ment for the module
PC5020 VAUX: 550 mA.
Subtract the listed rating for each keypad,
expansion module and accessory connected to
VAUX or Keybus.
BELL: 700 mA.
Continuous Rating.
3.0 A.
Short Term. Available only with stand-by bat-
tery connected.
PC5200 VAUX: 1.0 A.
Continuous Rating. Subtract for each device
connected.
3.0 A.
Short Term. Available only with stand-by bat-
tery connected.
PC5204 VAUX: 1.0 A.
Continuous Rating. Subtract for each device
connected.
3.0 A.
Short Term. Available only with stand-by bat-
tery connected.
PC5208 VAUX: 250 mA.
Subtract for each device connected. Subtract
the total load on this terminal from the
PC5020 VAUX/Keybus output.
PC5108 VAUX: 100 mA.
Subtract for each device connected. Subtract
the total load on this terminal from the
PC5020 VAUX/Keybus output.
Module Jumpers
System Zones
Assigned
J1 J2 J3
ON ON ON Zones disabled
OFF ON ON Zones 09 - 16
ON OFF ON Zones 17 - 24
OFF OFF ON Zones 25 - 32
ON ON OFF Zones 33 - 40
OFF ON OFF Zones 41 - 48
ON OFF OFF Zones 49 - 56
OFF OFF OFF Zones 57 - 64