EasyManua.ls Logo

DSC PC5020 - Keypad Zones

DSC PC5020
66 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation and Wiring: 2.10 Keypad Zones
9
LINKS1000 Answer
If the LINKS1000 cellular communicator is being used a zone
may be configured for LINKS1000 Answer to allow download-
ing to be performed in the event of telephone line failure.
When the LINKS1000 receives a telephone call it will activate the
RING terminal on the LINKS1000 circuit board. This terminal can
be used to violate a zone programmed as (24) LINKS1000
Answer (see section 5.3 Basic Programming on page 20), causing
the panel to seize the telephone line and begin communication
with the downloading computer.
The zone programmed as LINKS1000 Answer ALWAYS requires a
single EOL resistor (5600) and must be wired according to this
diagram:
NOTE: The LINKS1000 Answer zone is only required for down-
loading to the panel via the LINKS1000, or for remotely connect-
ing to the Escort5580 module via the LINKS1000.
NOTE: When using the LINKS1000, Busy Tone Detection must not
be used.
NOTE: Keypad zones cannot be used for 24 Hour Supervisory or
LINKS1000 Answer.
LINKS 2X50/LINKS 3000/Skyroute™
Refer to the LINKSX50, LINKS3000 and Skyroute™ Installation
Manuals for wiring and installation details.
2.10 Keypad Zones
Keypads with zone inputs can be connected to devices such as
door contacts. This saves you from running wires back to the
control panel for every device.
To install the keypad, open the keypad plastic by removing the
screw at the bottom of the unit. Locate the five terminals on the
keypad circuit board. Connect the four Keybus wires from the
control panel: the red wire to R, the black to B, the yellow to Y
and the green to G.
To connect the zone, run one wire to the Z terminal and the
other to B. For powered devices, use red and black to supply
power to the device. Run the red wire to the R (positive) terminal
and the black wire to the B (negative) terminal.
When using end of line supervision, connect the zone according
to one of the configurations outlined in section 2.9
“Zone Wir-
ing”
on page 7.
NOTE: End of line resistors must be placed on the device end of
the loop, not at the keypad.
NOTE: Keypad zones do not support DEOL resistors.
Assigning Keypad Zones
When using keypad zone inputs, each input used must be
assigned a zone number in Installer’s Programming.
First, ensure that you have enrolled all installed keypads into the
desired slots (see section 2.6 Keypad Assignment on page 7).
Next, enter programming section [020] to assign the zones.
There are eight programming locations in this section, one for
each keypad slot. Enter a 2-digit zone number for each of the
keypad zones. This number must be entered in the location cor-
responding to the keypad to which each zone is connected.
NOTE: If a keypad zone input is assigned on zone number from 1
to 8, the corresponding zone cannot be used on the main control
panel.
Once the keypad zones are assigned, you must also program zone
definitions and zone attributes (See Section 5.3 Basic Program-
ming PWS Sect 3 [001]-[004] and Section 5.4 Advanced System
Programming PWS Sect 4 [101]-[164])

Table of Contents

Other manuals for DSC PC5020

Related product manuals