Programming Sections: 5.6 Communicator Programming
39
[347] MISCELLANEOUS REPORTING CODES
1, 2 Failure to Communicate
(Phone Numbers 1 & 2)
When events fail to communicate to either telephone number, this reporting code will be transmit-
ted the next time a communication is successful. The information will be transmitted in the following
order.
OLD EVENT(S)
FAILURE TO COMMUNICATE (PHONE #1)
NEW EVENT(S)
If multiple FTC’s occur, this FTC reporting code will create blocks of old information. The FTC report-
ing code does not follow any call direction “group”. This code is sent to every group’s call directions
on transmission of failed event transmissions. When event(s) fail to communicate to a telephone
number, there will not be an attempt to communicate again until another event is sent to that
phone number.
3 Event Buffer is 75% Full
Since Last Upload
When the internal 256 Event Buffer is 75% full since the last successful upload to a computer, this
reporting code will be transmitted.This code is sent to the System Maintenance Call Direction Group.
4, 5 DLS Lead In and Lead Out The DLS Lead Out Reporting codes are transmitted by the panel when DLS has completed a success-
ful DLS call to the panel. The DLS Lead In reporting code is transmitted two ways:
After the panel has been successfully called by DLS, but before the panel calls DLS back via the
Downloading Telephone Number when Callback is enabled.
Upon a User Initiated Call-up.
These reporting codes are sent to the System Maintenance Call Direction Group.
6, 7 Zone Fault Alarm &
Restore
This reporting code is sent when a zone has entered the Fault state. This refers to the short state on
DEOL hardwired zones and/or a loss of supervisory on a wireless zone. These codes are sent to the
System Maintenance Call Direction Group.
9, 10 General Zone Low Bat-
tery Alarm and Restore
Codes
These reporting codes are sent to report a Low Battery condition on the system. Individual zones are
not described using the Pulse formats however the individual zones will be logged to the event
buffer. SIA and Contact I.D. formats will identify the zone with the condition. A zone trouble will be
displayed immediately but the transmission may be delayed (see Section [377]). A low battery restore
may only take place after the alarm sensing device has been tampered and the batteries have been
changed. These reporting codes are transmitted to the System Maintenance Call Direction group.
[348] TEST TRANSMISSION REPORTING CODES
1, 2 Walk Test Begin / End These reporting codes are sent when Walk test is initiated and terminated.
3 Periodic Test
Transmission with
Trouble
This reporting code will be sent to the central monitoring station instead of Periodic Test Transmis-
sion when the programmed interval and time of day have elapsed and one or more of the following
unrestored condition exists:
Fire Zone Trouble (Zones 1-64)
Fire Zone Alarm (Zones 1-64, Two-Wire Smoke)
Fire Trouble (Two-Wire Smoke)
Fire Tamper/Low Sensitivity (Wireless/AML Zones 1-32)
Fire Zones Bypassed (Zones 1-64)
Fire Supervisory (Wireless/AML Zones 1-32)
Fire Supervisory (Wireless/AML Zones 1-32)
AC Trouble (PC5020, PC520X)
Battery Trouble (PC5020, PC520X)
Aux Trouble (PC5020)
Bell Trouble (PC5020)
Module Supervisory
Ground Fault (PC5700)
TLM Trouble (PC5020, PC5700 Line 1-2)
FTC Trouble
This reporting code is sent to the System Test Transmission Call Direction Group.
4 Periodic Test
Transmission
The panel can send a Periodic Test Transmission Reporting Code at the programmed Test Trans-
mission Time of Day (See section[378]). The Test Transmission Cycle 9 (See Section [377])
determines the period of time between tests. When the test transmission cycle is programmed, the
panel will send a test transmission the following day. This will indicate the beginning of the new test
transmission cycle to central station.
5 System Test When the [*] [6] [Master Code] [4] command is used to perform a manual system test, this reporting
code is sent to test the communicator. This code is sent to the System Test Transmission Call Direc-
tion Group (see section [*] [6] User Functions on page 15).
6 LINKS1000 Test Transmis-
sion Code
The system will send this reporting code via the LINKS1000 cellular transmitter at the programmed
interval (See Test Transmission Cycles Section [378])) and time of day (See Section [377]) of the LINKS
Periodic Test Transmission. This code is sent to the System Test Transmission Call Direction Group.
[349] PC5700 MAINTENANCE REPORTING CODES
1, 2 PC5700 Ground Fault
Trouble & Restore
These codes are sent when a Ground Fault Trouble/Restore occurs on the PC5700.
[320]-[349] REPORTING CODES