Programming Sections: 5.3 Basic Programming
21
21 24 Hour Latching
Tamper.
This zone type, when violated, will cause arming of the system to be inhibited until the valid Installer code is
entered. If this zone type is violated, the Installers code must be entered ([*][8] Installers Code) before the sys-
tem can be armed.
22 Momentary Key-
switch Arm.
A keyswitch module may be connected to the zone programmed as Momentary Keyswitch arm. Momentary
activation of this zone to the alarm state will alternatively arm and disarm the system and silence alarms.
Tampers and Faults will only initiate their respective trouble sequence.
NOTE: The keypad will not display an indication when this type of zone is activated.
23 Maintained Key-
switch Arm
A Normally Open Keyswitch module may be connected to the zone programmed as Maintained Keyswitch
arm. In the restored state, the panel is disarmed. Only the violation of this zone type to the alarm state will
make the panel arm. Tampers and Faults will only initiate their respective trouble sequence
24 LINKS Answer Provides the LINKS with a forced answer for downloading. This zone is similar to a fire zone; the Supervision
Options (NC, EOL, DEOL) do not effect the functionality of the zone. The Restored state of this zone type is
5.6K, and the open state causes the panel to answer.
A 5.6K resistor must be placed across the LINKS’ RING terminal and zone terminal. Normally, the RING ter-
minal would be ground, providing 5.6K to the zone input. If the RING terminal opens, the panel will seize
the telephone line.
NOTE: This zone type must not be used for wireless zones.
25 Interior Delay Zone The Interior Delay Zone is normally used with motion detectors and has a standard exit delay time. If the
panel is armed, and a Delay zone is violated during the Exit Delay (or the Away function key is used), the Inte-
rior Delay Zone will be active at the end of the Exit Delay. This zone will cause an instant alarm when violated.
This zone type will follow the Entry Delay time provided that a Delay zone is violated first. If the panel is
armed, and a Delay zone is NOT violated during the Exit Delay (or the Stay function key is used, or [*][9]
armed), a violation of this zone type will initiate Entry Delay 1.
26 24 Hour Non-Alarm
These zones are active at all times but do not cause an alarm, and do not show up in alarm
memory. Zone Attributes such as Zone Bypassing and Door Chime affect the functionality of this
zone. A 24 Hour Non-alarm zone may be used for Zone Follower automation applications.
NOTE: This zone type will be active in Walk Test. Tampers and Faults. Zones programmed as 24 Hour Non-
alarm type will not cause alarms. Alarms on this zone will not initiate Downlook
27 Delayed 24Hr Water-
flow
These zones will follow the waterflow Delay Timer. When a delayed waterflow zone is violated, the water-
flow timer will start, (any subsequent delayed waterflow zones that become active do not reset or abort this
timer). If there are still delayed waterflow zones open when the waterflow timer expires, the panel will go
into alarm and communicate the event(s) regardless of the armed state.
28 Instant 24Hr Water-
flow
A Waterflow alarm is a Fire alarm. The Fire related bells and Aux functions are activated. This Zone type func-
tions similar to Type 27 (Delayed 24Hr Water-flow), but does not follow the Water-flow Delay Timer. When
this zone is violated, it will immediately go into alarm. This zone type always uses a single EOL configuration.
29 Auto Verified Fire
Zone
The control panel will cycle power to a smoke detector or device to ensure the alarm condition is still present
when power is restored. The alarm sequence for the zone is indicated below:
Step #1 Duration 20 Seconds Sensor Reset
Step #2 Duration 10 Seconds Settle Time (Power Up)
Step #3 Duration 60 Seconds Check for Verified Alarm
NOTE: If another Fire device detects Fire during the Auto Verify or Delay sequence, the sequence is termi-
nated and alarms are immediately generated for all pending zones. This applies to all other Fire zones on the
system regardless of the partition assignments (i.e. two fire alarms anywhere on the system will cancel all
pending fire delays and create immediate alarms).
30 Fire Supervisory Zone
When this zone is violated, the system turns on the keypad buzzer, and communicates the supervisory alarm
condition to the monitoring station. The buzzer will not follow the Bell-Time-Out timer. To silence the buzzer,
a valid access code must be entered.
NOTE: The fire supervisory alarm is not affected by the water-flow silence inhibit option described in [018],
Sixth Option Codes, Pg 33
31 Day Zone A zone programmed with this type has different characteristics in the armed and disarmed state. In the dis-
armed state, violating this zone will sound the keypad buzzer but will not log or report the event. In the
armed state, violating this zone will sound the bell and communicate the event..
87 Delayed 24 Hour Fire
(Wireless)
Used only with wireless smoke detectors. Functions same as that of Zone Type [07].
88 Standard 24 Hour Fire
(Wireless)
Used only with wireless smoke detectors. Functions same as that of Zone Type [08].
[001]-[004] ZONE DEFINITIONS
Option Zone Type Description