EasyManua.ls Logo

DSC PC5020 - Page 32

DSC PC5020
66 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
26
.
Section Option On/Off Description
[013] - [018] SECOND SYSTEM OPTION CODES
[013]
Option
1
Zone Loop Type ON Normally Closed Loops. All zones are wired as normally closed circuits with returns con-
nected to a COM terminal. The end-of-line resistor is not required. An alarm will be gener-
ated when the circuit is opened.
OFF End-of-Line Resistors. All zones must be wired with an end-of-line resistor connected
between the ZONE and COM terminals. An alarm will be generated when the circuit is
opened or shorted. If the zone is programmed as a Fire zone, an open circuit will be
reported as a Fire Trouble, and a short circuit will be reported as a Fire Alarm.
[013]
Option
2
End-of-Line Option ON Double End-of-Line Resistors. All zones will use Double-End-of-Line resistors, except
Standard Fire, Delayed Fire, Supervisory, and LINKS Answer zone types. These zones must
be connected using the EOL resistor. Double EOL resistors enables detection of zone faults
and tampers. The tamper resistor (5.6K) is placed across the alarm activating device, and
the single EOL resistor (5.6K) is placed between the alarm and tamper contacts. This
configuration will allow the panel to detect zone faults (zone shorted), zone tampers
(open zone), zone alarms (11.2K), and restored zones (5.6K).
If the zone is disarmed and placed in the tamper (open) or fault (short) state, trouble
beeps will generate on all system keypads until a key is pressed. A zone tamper will be
sent to the monitoring station if programmed. If Section [701] Option 4 is ON (Latching
System Tampers), any system tamper will cause arming to be inhibited until the tamper is
restored and the Installer’s code is entered [*] [8] [Installer’s Code].
If the zone is armed and a tamper is activated, The tamper alarm and zone alarm will be
logged and transmitted. The zone will begin normal alarm sequence (Alarm, Bell, etc.).
OFF Single End-of-Line Resistors. All zones must have a 5.6K resistor across them. If the
zone is shorted or open, it will be in the violated state. If the zone is open and pro-
grammed as a fire zone, it will be in the trouble state.
NOTE: Zone Faults (Supervisories) on wireless zones will not cause an audible alarm while
armed.
[013]
Option
3
Trouble Display ON Panel Shows all Troubles While Armed. The panel will illuminate the Trouble LED
when any troubles are present on the System in both the armed and disarmed state.
OFF Panel Shows Only Fire Troubles While Armed. The panel will illuminate the Trouble
LED for all troubles while disarmed, but will only illuminate the LED for Fire Troubles while
armed.
NOTE: This option must be OFF if LCD5500 keypads older than version 2.00 are used.
[013]
Option
4
Tampers/Faults Display ON Tampers and Faults Do Not Show as Open. The panel will not illuminate the respective
Zone LED if the zone is in the Tamper or Fault states, only the Trouble LED will be on.
OFF Tampers and Faults Show as Open. The panel will illuminate the respective Zone LED if
the zone is in the Tamper or Fault states. The Trouble LED will also light.
5 Future Use
[013]
Option
6
Audible Exit Fault ON Audible Exit Fault is Enabled. If a non force-armable Delay 1 or Delay 2 type zone is left
open at the end of the Exit Delay, the Entry Delay will begin immediately and the bell or
siren will sound a steady alarm for the time programmed as Bell Timeout. This feature is
designed to immediately alert the user that their system has been armed incorrectly
OFF Audible Exit Fault is Disabled.
NOTE: For [*][9] arming, if Audible Exit Fault is enabled a violated zone will begin entry
delay as per Audible Exit Fault functionality. If this option is disabled, a violated delay zone
at the end of the exit delay will cause an instant alarm.
[013]
Option
7
Event Buffer Follows
Swinger Shutdown
ON Event Buffer Follows Swinger Shutdown. Once an event reaches its Swinger Shut-
down limit programmed in Section [370], it will no longer log events to the Event Buffer
until the Swinger Shutdown is reset. This avoids filling the Event Buffer with useless events
and prevents the panel from overwriting the entire buffer if a problem exists.
NOTE: The Event Buffer can be viewed with an LCD Keypad, Printed on-site using the
PC5400 printer module, or uploaded with DLS software.
OFF Event Buffer Logs Events past Swinger Shutdown.
[013]
Option
8
Fire Signaling ON Temporal Three Fire Signal. This cadence is as follows: (500ms ON, 500ms OFF, 500ms
ON, 500ms OFF, 500ms ON, 1.5 sec. OFF).
OFF Standard Pulsed Fire Signal. All fire bells will sound with the standard 1 second on/1
second off fire bell cadence.
NOTE: Only Zone Definitions [07], [27], [28], [29], [08], [87], and [88] (along with the [F]
Key) will use this signaling if enabled. All other zone definitions set to pulse will use stan-
dard pulse cadence.

Table of Contents

Other manuals for DSC PC5020

Related product manuals