Front Panel Configuration
34
8.1 ACCESSING THE FRONT PANEL EDITOR (FPE)
To enter the ‘configuration mode’ press both the DOWN and INFO
buttons together.
NOTE:
NOTE:NOTE:
NOTE:-
--
-
To exit the front panel configuration editor
To exit the front panel configuration editor To exit the front panel configuration editor
To exit the front panel configuration editor and activate your changes,
and activate your changes, and activate your changes,
and activate your changes, press
press press
press and hold
and hold and hold
and hold the
the the
the
button. Ensure you have saved any changes you have made by pressing the
button. Ensure you have saved any changes you have made by pressing the button. Ensure you have saved any changes you have made by pressing the
button. Ensure you have saved any changes you have made by pressing the
button first.
button first.button first.
button first.
NOTE:
NOTE:NOTE:
NOTE:-
--
-
When the editor is visible, it is automaticall
When the editor is visible, it is automaticallWhen the editor is visible, it is automaticall
When the editor is visible, it is automatically exited after 5 minutes of inactivity to ensure
y exited after 5 minutes of inactivity to ensure y exited after 5 minutes of inactivity to ensure
y exited after 5 minutes of inactivity to ensure
security.
security.security.
security.
8.1.1 EDITING A PARAMETER
• Enter the editor as described above.
• Press to select the required ‘page’ as detailed in the configuration suite tables.
• Press (+) to select the next parameter or (
-)
to select the previous parameter within the current page.
• When viewing the parameter to be changed, press the
button. The value begins to flash.
• Press (+) or (
-)
to adjust the value to the required setting.
• Press
to save the current value, the value ceases flashing.
Press and hold the
button to activate the changes you have made and exit the editor. the configuration icon
is removed from the display.
8.2 ADJUSTABLE PARAMETERS (CONFIGURATION EDITOR)
When viewing the configuration editor, Press to select the required ‘page’ as listed below.
Front Panel Configuration Editor
(Factory default settings are shown in bold italicised text)
Page FPE ID Parameter Values
DISPLAY
101 LCD Contrast 0%
102 Display Mode English (0), Icon Only (1)
103 Date and Time dd-mm-yyyy, hh:mm:ss
104 S1 Option Mains (0), Generator (1)
105 S2 Option Mains (0) Generator (1)
S2
201 Immediate S2 Dropout Off (0) On (1)
202 Under Voltage Trip (Generator Option) 0 V
203 Over Voltage Trip (Generator Option) 0 V
204 Under Frequency Trip (Generator Option) 0.0 Hz
205 Over Frequency Trip (Generator Option) 0.0 Hz
206 Under Voltage Trip (Mains Option) 0 V
207 Over Voltage Trip (Mains Option) 0 V
208 Under Frequency Trip (Mains Option) 0.0 Hz
209 Over Frequency Trip (Mains Option) 0.0 Hz
S1
301 Immediate S1 Dropout Off (0) On (1)
302 Under Voltage Trip 0 V
303 Over Voltage Trip 0 V
304 Under Frequency Trip 0 Hz
305 Over Frequency Trip 0 Hz
TIMERS
401 S1 Transient Delay mm:ss
402 Start Delay hh:mm:ss
403 Warming Up Time hh:mm:ss
404 S2 Fail Delay mm:ss
405 Elevator Delay mm:ss
406 Non-sync Transfer Time mm:ss.s
407 Check-Sync Transfer time mm:ss.s
408 Return Delay hh:mm:ss
409 Cooling Time hh:mm:ss
410 Fail to Stop Enable Disabled (0) Enabled (1)
411 Fail to Stop Delay mm:ss
412 S2 Transient Delay s.s
413 LCD Scroll Timer hh:mm:ss