DSE Model 5210 Automatic Start Engine Management and Instrumentation System Operators Manual
057-011 5210 OPERATING MANUAL ISSUE 5.1 18/06/2007 AM 39
Engine settings – Crank disconnect Value
Crank disconnect on generator frequency 21.0 Hz
Crank disconnect oil pressure <Disabled>
Check oil pressure prior to starting Yes
Engine settings – speed Value
Underspeed trip
#
1250 RPM
Underspeed prealarm
#
1350 RPM
Overspeed prealarm
#
1650 RPM
Overspeed trip
#
1750 RPM
Overspeed overshoot 0%
Plant battery settings Trip Return
Under volts warning
#
8.0 V DC 9.0 V DC
Over volts warning
#
33.0 V DC 32.0 V DC
Charge alternator warning
#
8.0 V DC N/A
Exercise scheduler settings Value
Enable exercise scheduler No