51
9.12 Chimney Sweep Function

table below.
Chimney Sweep Function enables boiler to generate
maximum heating power.
After activation, boiler power % can be adjusted from
minimum (0%) to maximum (100%) in DHW mode.
A. Press and hold and at the same time for 6
seconds. When the function is enabled, displays
shows “On” for few seconds followed by program
row “303” alternating with % of boiler power.
B. Press or to gradually adjust power
(increments of 1%).
C. To exit press both buttons and together for
at least 6 seconds.
D. If value of CO
2
-O2

and their relative distances. See Figure 11-1.
If necessary, replace electrodes and position them
correctly. If problem persists, use "COMBUSTION
ADJUSTMENT FUNCTION (CO
2
%)". See Section 11
General Maintenance, Figure 11-1 Electrodes. If problem
persists, use Section 9.8 Automatic Calibration
Function, and Section 9.9 Manual Calibration
Function.
NOTICE
Press 
temperature for 15 seconds.
Use a regularly calibrated combustion analyzer
for combustion analysis.
During normal operation boiler performs
combustion control cycles. In this phase CO
values higher than 400 ppm can occur for brief
periods of time.
(*) Automatically calculated from the PCB
9.14 Check Firing Rate
1.
Measure input, if a gas meter is installed in the
system.

Activate some heating zones to dissipate heat.

Function.
Use ½, 1 or 2 cu ft dial on gas meter. Measure
time required for two or more complete
revolutions. Measure time
for one or more
minutes.
Calculate input.
9.13 Combustion Adjustment Function (CO2%)
This function sets out to partially adjust the value of
CO
2
%. Use the following procedure:
1.
Press buttons and together for at least 6
seconds. When the function is enabled, displays
shows “On” for a few seconds followed by program
row “304” alternated with the % of boiler power;
2.
After burner is lit, boiler reverts to maximum
DHW power (100). When display shows "100" it is
possible to partially adjust value of CO
2
%;
3.
Press and . Display shows "00" alternating
with function number "304" (

4.
Press to raise or lower the amount of CO
2
(from -0.3% to +0.3%);
5.
Press to save new value. Power value "100" will
show on display again. Boiler continues operating at
maximum DHW power.
This procedure can be used to adjust CO
2
to ignition
power and minimum power by pressing after
performing step 5 above.
6.
After saving the new value (step 5 above), press
to set boiler to ignition power. Wait for value
of CO
2
to stabilize. Adjust as described in step 4 of
procedure (power value is a number <> 100 and <>
0). Repeat step 5 to save.
7.
Press to adjust boiler to minimum power. Wait
for value of CO
2
to stabilize. Go to step 4 to adjust
(power value = 00);
8.
Exit function by pressing and together for at
least 6 seconds, see step 1.
9 - START UP PROCEDURE
Combustion
Table
Gas A (Natural Gas) Gas E (LPG)
DCBF-100
DCCF-115 & 150
DCBF-125
DCBF-165
DCCF-205
All
CO2 % O2 % CO2 % O2 % CO2 % O2 % CO2 % O2 %
Maximum
power
(100%)
Nominal value 9.0 4.9 8.7 5.4 9.0 4.9 10.0 5.7
Permitted
value
8.5
9.5 4.0 - 5.7 8.2 – 9.3 4.3 – 6.3 8.5 – 9.5 4.0 – 5.7 9.5 – 10.5 4.9 – 6.4
Ignition
power (*)
Nominal value 8.7 5.4 8.7 5.4 8.7 5.4 10.8 4.8
Permitted
value
8.2 - 9.3 4.3 – 6.3 8.2 – 9.3 4.3 – 6.3 8.2 – 9.3 4.3 – 6.3 10.3 - 11.3 3.7 – 5.2
Minimum
power (0%)
Nominal value 8.8 5.2 8.8 5.2 9.0 4.9 9.8 6.0
Permitted
value
8.2 - 9.3 4.6 – 6.3 8.2 – 9.3 4.3 – 6.3 8.5 – 9.5 4.0 – 5.7 9.3 – 10.3 5.2 – 6.7
240013375 REV A, [07/01/2021]