EasyManua.ls Logo

Dunkirk DCBF-125 - Safety Relief Valve and Air Vent; Trim Piping; System Piping

Dunkirk DCBF-125
138 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Check Local Check Local
Codes For Codes For
Maximum Maximum
Distance To FloorDistance To Floor
Safety Relief
Valve
Do not use
plastic pipe see
Warning above.
FIGURE 6-1 Safety Relief Valve
31
6.3 Safety Relief Valve and Air Vent

provided with boiler. See Figure 6-1.
Install safety relief valve with spindle in vertical
position.

safety relief valve.
Install discharge piping from safety relief valve.
Do not use plastic pipe.
Use ¾" or larger pipe.
Use pipe suitable for temperatures of 375°F
(191°C) or greater. Do not use plastic pipe on
safety relief valve.
Individual boiler discharge piping shall be
independent of other discharge piping.
Size and arrange discharge piping to avoid
reducing safety relief valve relieving capacity
below minimum relief valve capacity stated on
rating plate.
Run pipe as short and straight as possible to
location protecting user from scalding and
properly drain piping.
Install union, if used, close to safety relief valve
outlet.
Install elbow(s), if used, close to safety relief
valve outlet and downstream of union (if used).
Terminate pipe with plain end (not threaded).
WARNING
Burn and scald hazard. Safety relief valve could
discharge steam or hot water during operation.
Use pipe suitable for temperatures of 375°F
(191°C) or greater. DO NOT use plastic pipe.
Install discharge piping per these instructions.
!
6 - HYDRONIC PIPING
6.4 Trim Piping
Temperature - Pressure Gauge. Install temperature
pressure gauge using tee and bushing provided in
near boiler piping on supply side. See Figure 6-2.
Some boiler models may have integral drain valve
located inside jacket directly underneath pump.
Install external drain valve as required.
6.5 System Piping
Ensure plugs are removed from boiler water
connections.
See Figure 6-5 for basic system piping


prevention device.
Single boiler system. See Figures 6-2, 6-5, for
general guidance. Additional considerations:
Boiler control only supports integrated pump.
Installer responsible for integration of multiple

external control.
Boiler control allows domestic hot water
prioritization.


Manufacturer recommends installing an isolation
and purge valve to use during commissioning to
ensure the boiler does not shut down due to over-

Do not install isolation valve between boiler and any

If soldering piping to boiler, avoid over heating and
damaging seals and gaskets.
Connect system valve pipe work to the boiler.
Route pressure relief valve discharge piping to the

 See Figure 6-1.
Verify all drain valves are closed.
When installing safety relief valve it must
be installed in a vertical position with
spindle at top.
Note
240013375 REV A, [07/01/2021]

Table of Contents

Other manuals for Dunkirk DCBF-125

Related product manuals