9.17 Adjusting Maximum Heating Power
Maximum boiler heating power can be reduced to suit
requirements of heating system it serves.
Table showing parameter P13 values according to
desired maximum power model is shown for each single
boiler.
To access and edit P13 values, proceed as described in
Section 9.15 Parameter Settings.
Boiler Model - PARAMETER P13 (%)/ Heating Output
Btu/h KW DCBF-125 DCCF-150
20,400 6.0 0 0
23,800 7.0 4 3
27,200 8.0 7 6
30,700 9.0 11 9
34,100 10.0 15 12
40,900 12.0 22 18
47,700 14.0 30 24
54,500 16.0 37 29
61,400 18.0 44 35
68,200 20.0 52 41
75,100 22.0 59 47
81,900 24.0 67 53
88,700 26.0 74 59
95,500 28.0 80 65
102,300 30.0 88 71
109,200 32.0 96 75
112,600 33.0 100 80
9 - START UP PROCEDURE
Btu/h kW DCBF-165 DCCF-205
27,400 8.0 0 0
31,300 9.2 4 3
35,800 10.5 7 6
41,300 12.1 11 9
46,500 13.6 15 12
55,900 16.4 22 18
65,700 19.3 30 24
74,500 21.8 37 29
83,200 24.4 44 35
92,300 27.0 52 41
101,900 29.9 59 47
110,000 32.2 67 53
118,000 34.8 74 59
127,000 37.2 80 65
136,900 40.1 88 71
145,300 42.6 96 75
151,700 44.4 100 80
Btu/h kW DCBF-100 DCCF-115
17,060 5.0 0 0
20,473 6.0 4 3
23,885 7.0 7 6
27,297 8.0 11 9
30,709 9.0 15 12
34,121 10.0 18 15
40,946 12.0 25 21
47,770 14.0 35 28
54,594 16.0 45 35
61,419 18.0 57 45
68,243 20.0 68 55
75,067 22.0 80 65
81,891 24.0 95 75
85,400 25.0 100 80