To RESET boiler press button for at least 2 seconds.
For other error codes not described in table please contact manufacturer at 1(800) 325-5479.
13 - TROUBLE SHOOTING
13.1 Error Messages and Resetting the Boiler - continued
Anomalies Only Displayed in the Fault History
E62
Anti-wind activation with increase of the minimum
fan speed

E63/E65 Combustion level out of range 
E65
Maximum value of the speed reached / correction of


E67 Anti-wind activation at maximum power 
E69 Combustion level out of range 
E70
Flame signal problem/micro interruption of the

Check cable and integrity of the sensing electrode, verify the
continuity between burner and earth.
E73  Review and monitor other codes such as E53 and E92
Error Description Operation
135 Internal error Verify all cables. Replace PCB.
160 Fan fault Check fan and cable
162/317 Incorrect power supply frequency. Incorrect power supply frequency.
169 Flue pressure switch (contact open)
Check pressure switch and cable.

164/384
 Check correct operation of T. gas valve.
165/385 Input voltage too low. Check power supply
E178
Low return water temperature / anti-freeze
function active
Check the return water sensor, check the circulator, check the
correct circulation of the water. Boiler will exit status when
condition is resolved.