35
5. PRESET SOURCE
Allows the user to change between P1,P2,P3, and P4 on the keypad or through TB2 (see Figure
12). Note: the user changes the programmed presets in “Menu L: PROCESS”.
TERM
KEYPAD
6. PRESET 1 SOURCE
Allow the user to change what “P1” corresponds to. For example, “P1” can be set to “POT”,
but by being in “LOCAL” and “MANUAL” mode, one can use P2, P2, and P3 from the keypad,
but have the external potentiometer be enabled when “P1” is selected. “PULSE” corresponds
to “TB2-17”, which is the Follower Pulse Pickup Input.
POT
PULSE
KEYPAD
7. MAN START SOURCE
Allows the user to change how the control starts in “MANUAL” mode.
TERM
KEYPAD
8. AUTO START SOURCE
Allows the user to change how the control starts in “AUTO” mode.
SERIAL (for use with the ethernet IP add on)
TERM (default)
9. AUTO SETPNT SRC
Allows the user to change which setpoint reference is used.
SERIAL (for use with the ethernet IP add on)
TERM (default)
10. STOP SOURCE
Allows the user to change how to stop the control.
TERM (external stop button via TB2)
TERM&KPD (external stop button and keypad)