2.4 Environmental Ratings
Operating temperature range: 0°C to 40°C (enclosed or panel mount)
Storage temperature: -10°C to 75°C maximum
Humidity: 95% non-condensing
Elevation: to 1500 meters without derating
2.5 Electrical Noise
The control is immune to showering arc noise as specified by NEMA 519 test procedures.
Operation will not be affected by a 5 watt, 2-way radio transmission with the enclosure
door closed.
Noise Immunity and Radiation
The controller complies with FCC, part 15B, of federal regulation #47 as a Class A digital
device when operated in a defined enclosure and installed in accordance with our
instructions; third party verification is required.
EMI Susceptibility: Complies with IEC 801(1984)-3, class 2. It operates without fault or
disturbance under the specified level of radiated EMI (Performance Criteria 1).
2.6 Enclosures
Available in NEMA Type 1 (Dynamatic Part Number: 015-002000-0300)
Other enclosures available upon request (lead times may vary)
2.7 Weight
Panel Mounted Controller: 8.3 lbs. (base unit)
460/230VAC : 120VAC transformer: 24 lbs. (panel mounted)
2.8 Dimensions (see Figures 3-6)
Main Board: Main Board - 8.5"H x 9.25"W x 2.25"D
Panel Mounted (Standard):
Keypad: 4.875"H x 4.875"W x 1.375"D
2.9 Reliability
Mean Time Between Failures: 50,000 hours
2.10 Codes and Standards
National Electrical Code (NEC) compliant