CV3100 series and MINI series high performance general purpose inverter instruction manual
5-16
Senior Function
Function
Code
Name &
Definition
Set Range
Minimun
Unit
Factory
Default
Communi
cation
Address
Modify
PA.00
Zero
frequency
running
threshold
0.0050.00Hz
0.01Hz
0.00Hz
0A00H
PA.01
Zero
frequency
hysteresis
0.0050.00Hz
0.01Hz
0.00Hz
0A01H
PA.02
Energy
consuming
brakinginiti
al voltage
600750V
1V
700V
0A02H
PA.03
Energy
consuming
braking
action
percentage
10100
1%
50
0A03H
PA.04
Input
phase-failur
e protection
& Cooling
fan control
0Enable & Fan automatic control
1Enable & Fan working during
power on
2Disable & Fan automatic control
3Disable & Fan working during
power on
1
0
0A04H
PA.05
UP/DOWN
terminal
modifying
speed
0.01Hz100.0Hz/S
0.01Hz/S
1.00Hz/
S
0A05H
PA.06
Over
modulation
enabling
0Forbidden
1Allowable
1
0
0A06H
×
PA.07
Timer
value seting
065536S
1S
0
0A07H
×
PA.08
The Rang
of AO1
output
0010V/020mA
1210V/420mA
1
0
0A08H
×
PA.09
Reserved
PA.10
Reserved
PA.11
Reserved
PA.12
Reserved

Table of Contents