Configuration Using the PROFIBUS Configuration File
C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com 17
GND Fault Trip Mode Motor Insight 0 = Trip on GND fault
1 = Alarm-no-trip—default
Under Current Trip Level Motor Insight 10–90% of FLA (50) default
Under Current Trip Delay Motor Insight 1–60 seconds (5) default
Low Power Trip Level Motor Insight Setting is in kW x 100
Default value is the minimum value in the range.
Low Power Trip Delay Motor Insight 1–60 seconds (5) default
High Power Trip Level Motor Insight Setting is in kW x 100
Default value is the minimum value in the range.
High Power Trip Delay Motor Insight 1–60 seconds (5) default
% Current Unbalance Trip Level Motor Insight 1–30% (15%) default
Current Unbalance Trip Delay Motor Insight 1–20 seconds (10) default
Under Voltage Trip Level Motor Insight 170–264 V (216 V) CC441BA, C441BB
323–528 V (432 V) C441CA, C441CB
489–660 V (540 V) C441DA, C441DB
Under Voltage Trip Delay Motor Insight 1–20 seconds (10) default
Over Voltage Trip Level Motor Insight 170–264 V (264 V) C441BA, C441BB
323–528 V (528 V) C441CA, C441CB
489–660 V (540 V) C441DA, C441DB
Over Voltage Trip Delay Motor Insight 1–20 seconds (10) default
% Voltage Unbalance Trip Level Motor Insight 1–20% (6%) default
Voltage Unbalance Trip Delay Motor Insight 1–20 seconds (10) default
Voltage Faults Trip Mode Motor Insight 0 = Trip on voltage fault
1 = Alarm-no-trip (inhibit start)—default
Jam Fault Trip Level Motor Insight 150–400% of FLA (300%) default
Jam Fault Trip Delay Motor Insight 1–60 seconds (5) default
Phase Loss Trip Delay Motor Insight 1–20 seconds (10) default
Restart Delay Motor Insight 0–500 seconds (10) default
Motor Fault Reset Delay Motor Insight 2–500 minutes (8) default
Motor Faults—Number of Restarts Motor Insight 0 = Manual, 1–4, 5 = Auto reset mode
Load Faults Reset Delay Motor Insight 2–500 minutes (20) default
Load Faults—Number of Restarts Motor Insight 0 = Manual, 1–4, 5 = Auto reset mode
Enable Load Faults Reset Delay Auto
Calculator
Motor Insight 0 = Reset Delay Auto Calc Off
1 = Reset Delay Auto Calc On
Run Transition % of FLA Motor Insight 25–125%
Run Transition Time Motor Insight 1–180 seconds
Phase Order Motor Insight 0x0000 = Phase Order Trip Disabled
0x0001 = ACB Phase Order
0x0002 = ABC Phase Order
MI ComLoss Timeout Motor Insight 0 = 65000 (msec)
MI ComLoss Behavior Motor Insight 0x0001 = Fault (Fail Safe) Relay Off
0x0002 = Hold Last State
Enable MI AuxRly GND Trip Indication Motor Insight 1 = Indication Enabled; 0 = No Indication (CP models only)
Enable MI AuxRly V Unbal Indication Motor Insight 1 = Indication Enabled; 0 = No Indication (CP models only)
Enable MI AuxRly I Unbal Indication Motor Insight 1 = Indication Enabled; 0 = No Indication (CP models only)
Enable MI AuxRly Under I Indication Motor Insight 1 = Indication Enabled; 0 = No Indication (CP models only)
Table 17. C441 Motor Insight Configuration File, continued
Parameter Name Location Notes