Configuration Using the PROFIBUS Configuration File
20 C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com
Enable Phase Reversal trip S611 0 = disable fault
1 = enable fault
Enable Overload on start trip S611 0 = disable fault
1 = enable fault
Enable Shorted SCR trip S611 0 = disable fault
1 = enable fault
Enable SCR Not Firing trip S611 0 = disable fault
1 = enable fault
Enable Over Temp trip S611 0 = disable fault
1 = enable fault
Enable GND Fault trip S611 0 = disable fault
1 = enable fault
Jam Trip Level S611 Current threshold setting for Jam fault. (valid only during bypass 150–400% rated motor fla)
Jam Trip Delay S611 Length of jam condition before fault in sec. (1–20)
Stall Trip Level S611 Current threshold setting for Stall fault. (valid only at end of start ramp 150–300% rated motor fla)
Residual GF Trip Level S611 Current threshold setting for GND fault trip. (in 0.1A) (1–100)
Residual GF Trip Delay S611 Length of GND fault condition before fault in sec. (1–20)
Residual GF Start Delay S611 Length of time from start to mask fault. (0–20sec)
Current Unbalance Trip Level S611 Current Imbalance fault threshold. (1–20%)
Current Unbalance Trip Delay S611 Length of current imbalance condition before fault. (1–20sec)
Load Disconnect Trip Level S611 Load disconnect fault threshold. (% motor fla: 1–50%)
Load Disconnect Trip Delay S611 Length of load disconnect condition before fault. (1–60sec)
Load Disconnect Source S611 Low Power
Low Current
Phase Loss Trip Level S611 Phase loss fault threshold. (% motor fla: 0–100%)
Phase Loss Trip Delay S611 Length of phase loss condition before fault. (1–20sec)
Start Control Level or Edge S611 S611 input configuration
0 = Edge triggered inputs
1 = Level triggered inputs
Fault Relay Configuration S611 S611 fault relay configuration—relay output enabled when:
0 = Faulted
1 = Not Faulted
Aux Relay Configuration S611 S611 aux relay configuration—relay output enable when:
0 = Faulted
1 = Not Faulted
2 = in Bypass
3 = Not in Bypass
4 = Motor Energized
5 = Not Motor Energized
User UI Edit Lock S611 Lock S611 User interface module. (Prohibits changing S611 settings from UI)
0 = unlocked
1 = locked
Comm loss Timeout in milli-seconds S611 Length of comloss before fault. (in .001 sec: 1–65000)
Comm loss behavior S611 1 = Fault
2 = Hold Last State
3 = Stop
S611 ComLoss Enable S611 0 = disable fault
1 = enable fault
Table 19. S611 Soft Starter Configuration File, continued
Parameter Name Location Notes