PROFIBUS I/O Parameters
C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com 27
input 2 MI Load Flt-Remaining Rstart Dly Seconds remaining before fault can be reset
input 2 MI Load Flt-Remaining Rstart Dly Seconds remaining before fault can be reset
input 2 MI Trip Reason 0x0001 = Restart Attempts Exceeded
0x0002 = Relay turned off (network/UI)
0x0004 = Contactor Failure
0x0008 = Under Current Trip
0x0010 = Overload Trip
0x0020 = GND Fault Trip
0x0040 = Current Unbalance Trip
0x0080 = Current Single Phase
0x0100 = Reserved (0)
0x0200 = High Power Trip
0x0400 = Over Voltage Trip
0x0800 = Under Voltage Trip
0x1000 = Voltage Unbalance Trip
0x2000 = Over Current Trip
0x4000 = Low Power Trip
0x8000 = Phase Reversal Trip
input 2 MI OL Status 0x0001 = Overload Tripped
0x0002 = GND Fault Tripped
0x0004 = High Power Tripped
0x0080 = Running
input 2 MI Error Code 0x0001 = Low Voltage Warning
0x0002 = High Voltage Warning
0x0004 = Voltage Unbalance Warning
0x0008 = Low Power Warning
0x0010 = Reverse Phase Warning
0x0020 = Current Unbalance Warning
0x0040 = Voltage Single Phase Warning
0x0080 = Current Single Phase Warning
0x0100 = GND Fault Warning
input 2 MI Aux Relay Trip Reason
(120 V Control Power models only)
0x0001 = NA
0x0002 = Relay turned off (network/UI)
0x0004 = Contactor Failure
0x0008 = Under Current Trip
0x0010 = Overload Trip
0x0020 = GND Fault Trip
0x0040 = Current Unbalance Trip
0x0080 = Current Single Phase
0x0100 = Mains Freq Fault
0x0200 = High Power Trip
0x0400 = Over Voltage Trip
0x0800 = Under Voltage Trip
0x1000 = Voltage Unbalance Trip
0x2000 = Over Current Trip
0x4000 = Low Power Trip
0x8000 = Phase Reversal Trip
Table 22. C441 Motor Insight Available IO Data for Cyclic Polling (PROFIBUS), continued