PROFIBUS Diagnostic Telegrams
C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com 41
11 24–31 Reserved Extended Diagnostic Data
12 32–39 Reserved
13 40–47 Reserved
14 48–55 Reserved
15 56–63 Reserved
16 64–71 Reserved
17 72–79 Reserved
18 80 1 = S611 Run S/S
81 Reserved
82 1 = S611 In bypass S/S
83 Reserved
84 Reserved
85 1 = S611 Faulted; 0 = S611 not faulted F/S
86–87 Reserved
19 88–92 Reserved
93 1 = Control from Net; 0 = local control S/S
94 1 = Permissive enabled; 0 = Permissive disabled S/S
95 Reserved
20 96 Reserved
97 1 = Overload trip F/S
98 1 –Jam trip F/S
99 1 = Stall trip F/S
100 1 = Current Imbalance trip F/S
101 1 = Load disconnect trip F/S
102 1 = Phase Loss trip F/S
103 1 = Mains voltage fault trip F/S
21 104 1 = Phase reversal trip F/S
105 1 = Shorted scr trip F/S
106 1 = SCR not firing trip F/S
107 1 = Pole over temp trip F/S
108 1 = Bypass failure trip F/S
109 1 = SCR over current trip F/S
110 1 = Contactor over current trip F/S
111 1 = Device fault trip F/S
Table 29. S611 Diagnostic Telegram, continued