Installer Menu Options i-on Range
Page 72
Type:
(nn=shortcut)
Active when:
Assign to
Partitions?
Pulsed?
Autoset Warning
(42)
50 160
The control unit starts the Calendar Set Warning
period (see page 85). Deactivates when the system
sets, or if a user defers or cancels the calendar set.
Assigned to all partitions by default.
Yes
Yes
User Defined (43)
The user switches the output on or off from the
keypad, or a remote control. Assign this output type
to any outputs that you want the user to control.
Note: You cannot assign this output type to a control
unit plug-by-output.
See “Programming User Defined Outputs” on page
73 for more details.
No
No
Line Fault (44)
The control unit detects a communications fault.
Deactivates when the communications fault clears
No
Yes
Courtesy Light
(45)
The entry or exit timer is running. The control unit
activates this output when the entry or exit time
starts, and deactivates the output 10 seconds after
the entry or exit time stops.
Yes
No
Installer On Site
(46)
The control unit is in Installer Menu. The control unit
activates the output when it enters Installer Menu,
and deactivates the output once it has successfully
left Installer Menu.
No
Yes
Duress Code (47)
A Duress code has been used. The control unit
activates this output whenever a user keys in a
Duress code, and deactivates the output when a
user or engineer resets the system.
Yes
Yes
HUA Confirm (48)
(Not available on EUR versions. Operates only
when BS8243 is enabled.) A confirmed Hold Up
Alarm (HUA) has occurred. The control unit
activates this output when:
a) Users have activated two separate Hold Up
Devices (HUDs) within the HUA confirmation time.
b) A HUD is active, and a tamper (in either order)
within the HUA confirmation time.
You can assign this output to one or more partitions.
Note that the HUDs (and tampers) must both be in
the same partitions as the output. The control unit
deactivates the output when a user or engineer
resets the system.
No
Yes
Lockset Unlocked
(49)
A Lock Set zone is active. The control unit activates
the output when the Lock Set zone is activated, and
deactivates the output when a Lock Set zone is
deactivated.
No
Yes