Enterprise Power Solutions Installation and Operation Guide
24
Copyright © 2008 Eaton Corporation. All Rights Reserved.
IPN 997-00012-56C September 2008
Step 2 - Fit the mounting brackets to the front of each battery module
"
Rack mounting bracket (two per module)
#
Mounting handle (two per module)
Step 3 - Fit battery modules into rack
1 Slide the battery modules into the rack starting at the bottom.
The battery modules are heavy (54.9kg/121 lb). A minimum of two
people are required to lift a module into a rack.
2 Secure the battery module to the front of the rack using the rack fixing
screws provided.
Step 4 - Connect cables
1 Connect the battery modules together in series (in two groups if two
battery circuit breakers are fitted).
Maximum 5 battery modules to be connected to each battery circuit
breaker in the EPS2/EPS5.
2 Connect from battery connector 1 (BATT 1) on the EPS2/EPS5 to the
cable plug on the first battery in group 1. Use the battery cable type
CKBATT-00 (see Spare Parts on page
66).
3 If required, connect from battery connector 2 (BATT 2) on the EPS2/EPS5
to the cable plug on the first battery in group 2.