Operation
Copyright © 2004-2009 Eaton Corporation. All Rights Reserved.
IPN 997-00012-35E December 2009
15
LVD Test
The LVD Test function allows the LVD contactors to be manually connected or disconnected
from DCTools or the keypad.
To activate the LVD Test function using DCTools
1 Start DCTools (refer to the Communications Options on page
30).
2 From the DCTools System Summary (Home) screen, go to LVD.
3 Click on LVD1 or LVD2 as required.
4 Click on the Front Panel LVD Test button.
5 Click the Apply Changes button.
To activate the LVD Test function using the keypad
1 Press : to go to Status View Mode.
2 Press 6 until the display shows LVD1 Test. If required, press 6 again to access LVD2
Test.
3 Press 8 to edit the LVD state.
4 Press 8 to confirm the change.
5 Press 6 7 to connect/disconnect the LVD as required.
6 Press 9 to go to Status View Mode.
7 Press 9 to go to Main Display Mode.
Rectifier Restart
This function temporarily restarts rectifiers that have either been shutdown automatically by
Load-based Rectifier Shutdown (LBRS) (see details on page
52), or manually shutdown from
DCTools or PowerManagerII.
Rectifiers shutdown will have the < (red) alarm LED on. Therefore, use this function to
restart all rectifiers to identify a faulty rectifier.
Load-based Rectifier Shutdown will continue to operate and some rectifiers will shut down
again after a period, depending on the LBRS configuration parameters. Rectifiers that were
previously shutdown manually will remain operating.
To restart shutdown rectifiers using the SM65 keypad
1 Press: to go to Status View Mode.
2 Press 6 until the display shows Auto Rect Shutdown
3 Press 8 to restart all shutdown rectifiers.
4 Press9 to go to Main Display Mode.