SM65 Supervisory Module Handbook
30
Copyright © 2004-2009 Eaton Corporation. All Rights Reserved.
IPN 997-00012-35E December 2009
Communications Options
The standard communications options for SM65 supervisory modules are shown below. For
other communications options refer to Worldwide Support on page
65.
See diagrams on page
2 for locations of the RS232 and Ethernet connectors.
Direct Connection
"
SM65 supervisory module
#
PC/laptop with
PowerManagerII and/or
DCTools. See setup details on
page
33.
$
RS232 null modem cable
(protocol: S3P)
%
SM30 RS232 comms cable
(P/N 410-00226-93A)
Ethernet
"
SM65 supervisory module
#
PC/laptop with
PowerManagerII and/or
DCTools (see setup details on
page
33), or web browser
(see details on page
35), or
Network Management System
using SNMP (see details on
page
34).
$
Communications network.
Protocol: S3P/IP. See
Ethernet Setup on page
33.
PSTN Modem
"
SM65 supervisory module
#
PC/laptop with
PowerManagerII and/or
DCTools. See setup details on
page
33.
$
RS232 modem cable
(straight-thru)
%
SM30 modem cable (P/N
410-05727-46A for DB9
modem connector, P/N
410-05723-63B for DB25
modem connector)
!
PSTN modem
&
PSTN network. Protocol: S3P