Step 10 - Reset any LVD controllers to Auto
If any LVD controllers were set to Manual Connect in Step 1 then reset them to
Auto.
Refer to the DC power system Installation Guide for information on how to set
the LVD Auto/Manual selector switch.
Procedure complete
Replacing a standard bracket mounting SM65
Before you start, you need
A PC with the DCTools software installed.
A copy of the appropriate SM65 configuration file, which can be one of the following -
the old configuration file, a backed-up configuration file or a modified default
configuration file.
A null modem cable.
Step 1 - Set any LVD controllers to Manual Connect
To prevent an accidental operation of an LVD contactor (and disconnection of
the battery or load equipment) set any LVD controllers to Manual Connect.
Refer to the DC power system Installation Guide for information on how to set
the LVD Auto/Manual selector switch.
Step 2 - Attach the two mounting brackets to the SM65