Maintenance
Copyright © 2004-2009 Eaton Corporation. All Rights Reserved.
IPN 997-00012-35E December 2009
45
Replacing an SM65 mounted in a slider magazine
Before you start, you need
• A PC with the DCTools software installed.
• A copy of the appropriate SM65 configuration file, which can be one of the following -
the old configuration file, a backed-up configuration file or a modified default
configuration file.
• A null modem cable.
Step 1 - Set any LVD controllers to Manual Connect
To prevent an accidental operation of an LVD contactor (and disconnection of
the battery or load equipment) set any LVD controllers to Manual Connect.
Refer to the DC power system Installation Guide for information on how to set
the LVD Auto/Manual selector switch.
Step 2 - Withdraw the old SM65 from the rack
1 Loosen the locking screw.
2 Press the two latches and pull the SM65 out.