Eaton SPD Series for Mounting External to Electrical Distribution Equipment Installation Manual IM01005031E—Rev 09 57
TTaabbllee 1122.. PPoowweerr XXppeerrtt SSPPDD MMooddbbuuss RReeggiisstteerr MMaapp ((CCoonnttiinnuueedd))
RReeggiisstteerr NNaammee AAttttrriibbuutteess DDeessccrriippttiioonn
Range: 0 to 1500
8958
High Surge Event
Time Stamp
UINT32 RO Stores the timestamp of high surge event. Timestamp will be stored in
epoch time
Array size: 1000 Array of 2000 registers
Default: 0
10958
High Surge Event
Phase Indicator
UINT8 RO Indicates in which the phase, medium surge event occurred.
Array size: 1000 Value Description
Default: 0
1
Phase A high surge event log
Enum 2 Phase B high surge event log
3
Phase C high surge event log
11458
High Surge Event Log
Index
UINT16 RO Index points to the latest high surge event log
Default: 0
Range: 0 to 1000
11459
Clear Surge Log
Events
BOOL RW NV Clear the high, medium and low surge event logs in phase A, B and C
1. Default value is zero 2. Writing 1 to the register will clear the surge
logs.
Default: 0
Range: 0 to 1
11460
Clear Surge Counts BOOL RW NV Clear the high, medium and low surge counts in phase A, B and C 1.
Default value is zero 2. Writng 1 to the register will clear the surge
counts.
Default: 0
Range: 0 to 1
11461
Indicates Power Xpert
SPD System faults
DWORD RO Power Xpert SPD system fault indication to user
Default: 0 Bit Description Coil
Bitfield
0
No faults
n/a
1
Error in logging
data to FRAM
n/a
2 NV memory
checksum error
n/a
11463
Total Low Surge
Counts
UINT32 RO Indicates total low surges occurred. This will be sum of phase A,
phase B and phase C low surge counts
Default: 0
Range: 0 to 999999
11465
Total Medium Surge
Counts
UINT32 RO Indicates total medium surges occurred. This will be sum of phase A,
phase B and phase C low surge counts
Default: 0
Range: 0 to 999999
11467
Total High Surge
Counts
UINT32 RO Indicates total high surges occurred. This will be sum of phase A,
phase B and phase C high surge counts
Default: 0
Range: 0 to 999999
11469
Sum of Surge Counts
of All Phases
UINT32 RO Indicates the total surge counts, This will be sum of low, medium and
high surges
Default: 0
Range: 0 to 999999