58 Eaton SPD Series for Mounting External to Electrical Distribution Equipment Installation Manual IM01005031E—Rev 09
TTaabbllee 1122.. PPoowweerr XXppeerrtt SSPPDD MMooddbbuuss RReeggiisstteerr MMaapp ((CCoonnttiinnuueedd))
RReeggiisstteerr NNaammee AAttttrriibbuutteess DDeessccrriippttiioonn
11476
Power Xpert SPD
Firmware Version
ASCII
STRING8 RO Power Xpert SPD firmware in the format of major & minor.
Array size: 6 Array of 3 registers
11479
Date Code STRING8 RO NV Date code as determined by test station, format : “yymmdd”. (MAE)
Array size: 7 Array of 4 registers
11483
Catalog Number STRING8 RO NV Catalog number assigned to the product. (MAE)
Array size: 20 Array of 10 registers
11497
Indicates the status of
N-G Green LED
BOOL RO Indicates the status of N-G green LED, 0:LED off 1:LED on. Indicates
protection status on N-G
Default: 0
11498
Indicates the status of
N-G Yellow LED
BOOL RO Indicates the status of N-G yellow LED, 0:LED off 1:LED on. Indicates
protection status on N-G
Default: 0
11499
Indicates the status of
N-G Red LED
BOOL RO Indicates the status of N-G red LED, 0:LED off 1:LED on. Indicates
protection status on N-G
Default: 0
11500
Indicates the status of
Phase A Green LED
BOOL RO Indicates the status of phase-A green LED, 0:Led off 1:LED on.
Indicates protection status on phase-A
Default: 0
11501
Indicates the status of
Phase A Yellow LED
BOOL RO Indicates the status of phase-A yellow LED, 0:LED off 1:LED on.
Indicates protection status on phase-A
Default: 0
11502
Indicates the status of
Phase A Red LED
BOOL RO Indicates the status of phase-A red LED, 0:LED off 1:LED on. Indicates
protection status on phase-A
Default: 0
11503
Indicates the status of
Phase B Green LED
BOOL RO Indicates the status of phase-B green LED, 0:LED off 1:LED on.
Indicates protection status on phase-B
Default: 0
11504
Indicates the status of
Phase B Yellow LED
BOOL RO Indicates the status of phase-B yellow LED, 0:LED off 1:LED on.
Indicates protection status on phase-B
Default: 0
11505
Indicates the status of
Phase B Red LED
BOOL RO Indicates the status of phase-B red LED, 0:LED off 1:LED on. Indicates
protection status on phase-B
Default: 0
11506
Indicates the status of
Phase C Green LED
BOOL RO Indicates the status of phase-C green LED, 0:LED off 1:LED on.
Indicates protection status on phase-C
Default: 0
11507 Indicates the status of
Phase C Yellow LED
BOOL RO Indicates the status of phase-C yellow LED, 0:LED off 1:LED on.
Indicates protection status on phase-C
Default: 0
11508
Indicates the status of
Phase C Red LED
BOOL RO Indicates the status of phase-C red LED, 0:LED off 1:LED on. Indicates
protection status on phase-C
Default: 0
11509 Alarm status UINT8 RO Power Xpert SPD alarm status, alarm is used to indicate protection
status
Default: 0 Value Description
Enum 0
Alarm OFF
1
Alarm ON
11510
Percentage of
protection on N-G
UINT16 RO Percentage of protection available on NG
Default: 0
11511
Percentage of
protection on Phase A
UINT16 RO Percentage of protection available on phase A
Default: 0
Appendix