Eaton SPD Series for Mounting External to Electrical Distribution Equipment Installation Manual IM01005031E—Rev 09 59
TTaabbllee 1122.. PPoowweerr XXppeerrtt SSPPDD MMooddbbuuss RReeggiisstteerr MMaapp ((CCoonnttiinnuueedd))
RReeggiisstteerr NNaammee AAttttrriibbuutteess DDeessccrriippttiioonn
11512
Percentage of
protection on Phase B
UINT16 RO Percentage of protection available on phase B
Default: 0
11513
Percentage of
protection on Phase C
UINT16 RO Percentage of protection available on phase C
Default: 0
11514
Silences the Alarm.
Setting the value, will
silence the Alarm
BOOL RW Silences the Alarm. Setting the value, will silence the alarm
Default: 0
11515
Ambient temperature
of SPD device
FLOAT RO Ambient temperature in Celsius
Default: 0
11517
General log Indicator UINT16 RO General log Indicator
Array size: 250 Value Description
Default: 0
0 No event occurred
Enum
1
Protection reduced on phase A
2 Protection reduced on phase B
3
Protection reduced on phase C
4
Protection reduced on neutral ground
5
Protection loss on phase A
6
Protection loss on phase B
7
Protection loss on phase C
8
Protection loss on phase neutral
ground
9 Alarm silenced
10
SPD powered off
11
SPD powered on
11767
General log
Timestamp
UINT32 RO Stores the timestamp of general log events. Timestamp will be stored
in epoch time. Time stamp can be verified using register 123.
Array size: 250
Array of 500 registers
Default: 0
12267
General log Index UINT16 RO
Index points to the latest general event log
Default: 0
Range: 0 to 250
12268
Clear General Log
Events
BOOL RW NV Clear general event logs 1. Default value is zero 2. Writing 1 to the
register will clear the general logs.
Default: 0
Range: 0 to 1
12269
Phase A Total Surge
Counts
UINT32 RO Sum of phase A high, medium and low surge counts
Default: 0
Range: 0 to 999999
12271
Phase B Total Surge
Counts
UINT32 RO Sum of phase B high, medium and low surge counts
Default: 0