3.2 Format, housing sizes and design
The MTX series is available in various capacity variants. All devices already
have an internal energy storage unit (power bank). In addition, external battery
banks with the same front format are delivered to enable an adaption to the au-
tonomous time.
For details, see the following list:
The device or the system can be set up in the combinations pictured below:
Fig. 3-2 Combination of the MTX series and the external battery bank.
All devices can be operated autonomously or complemented with one or more
battery banks. The total capacity of the energy storage is generated by the addi-
tion of the internal battery bank with the externally adapted battery banks. Nev-
ertheless, the limited charging current should always be taken into consideration
in these arrangements. Accordingly, the application of many battery banks
means a high autonomous period but also, at the same time, a correspondingly
increasing charging period and, with it, a significantly higher recovery time.