"VI"- USV 800-3000 VA
Error Codes
42
Warning / error
Symbol (blinking)
Acoustic signal
Error
number
Low battery bank status
(LOW BATTERY)
Signal every 2 sec.
-
Overload (OVERLOAD)
Signal every sec.
-
Overload (OVERLOAD)
Constant signal
43
Short circuit of UPS output
(SHORT)
Constant signal
14
Battery bank not connected
(NO BATTERY)
Signal every 2 sec.
-
Overcharge (OVER
CHARGE)
Signal every 2 sec.
-
Polarity fault (SITE WIR-
ING FAULT)
Signal every 2 sec.
-
Emergency dropping active
(EPO ACTIVE)
Signal every 2 sec.
-
Overtemperature (OVER
TEMPERATURE)
Signal every 2 sec.
41
Error with charging unit
(CHARGER FAILURE)
Signal every 2 sec.
45
Battery bank fault (BAT-
TERY Fault)
Signal every 2 sec.
-
Replace the battery bank
(BATTERY REPLACE)
Signal every 2 sec.
-
Battery bank voltage too
low (BAT TO LOW)
Constant signal
28
Battery bank voltage too
high (BAT TO HIGH)
Constant signal
27
Storage error (EEPROM
ERROR)
Signal every 2 sec.
-
DC link startup error (BUS
START FAIL)
Constant signal
01
DC link overvoltage (BUS
OVER)
Constant signal
02
DC link undervoltage (BUS
UNDER)
Constant signal
03
Inverter error, startup
(INVERTER START FAIL)
Constant signal
11
Inverter overvoltage
(INVERTER VOLT HIGH)
Constant signal
12
Inverter undervoltage
(INVERTER VOLT LOW)
Constant signal
13